| ASHRAE 52.2 | MERV 1–4 | Three particle-size ranges: 0.3–1, 1–3, and 3–10 μm | Lower MERV classes primarily describe performance in the larger-particle size range; efficiency requirements increase with class. | Compare the reported MERV value and test data for the complete filter, not the media description alone. |
| ASHRAE 52.2 | MERV 5–8 | 0.3–1, 1–3, and 3–10 μm | Progressively higher minimum particle-size efficiency requirements than MERV 1–4, particularly for larger particles. | The class is a standardized performance rating; pressure drop and dust-holding behavior should be checked separately. |
| ASHRAE 52.2 | MERV 9–12 | 0.3–1, 1–3, and 3–10 μm | Higher efficiency requirements across the test particle-size ranges than the lower MERV groups. | Useful for comparing tested filters when airflow, dimensions, and test conditions are also considered. |
| ASHRAE 52.2 | MERV 13–16 | 0.3–1, 1–3, and 3–10 μm | These classes have higher minimum efficiency requirements, including for the 0.3–1 μm size range. | Higher efficiency does not by itself establish suitability; verify airflow resistance and system requirements. |
| ISO 16890 | ISO Coarse | PM10-related performance; classification is based on the standard’s coarse-filter criteria. | Used for filters that do not meet the minimum ePM10 classification threshold. | The declared ISO Coarse percentage should be read with its test report and the applicable edition of the standard. |
| ISO 16890 | ePM10 | Particles in the PM10 fraction | The ePM10 class is reported with a percentage; an ePM10 classification requires at least 50% average efficiency for the relevant fraction. | For example, ePM10 60% expresses the declared class and efficiency percentage under ISO 16890 testing. |
| ISO 16890 | ePM2.5 | Particles in the PM2.5 fraction | The ePM2.5 class is reported with a percentage and requires at least 50% average efficiency for the relevant fraction. | For example, ePM2.5 70% identifies the reported ISO class; it is not a MERV value. |
| ISO 16890 | ePM1 | Particles in the PM1 fraction | The ePM1 class is reported with a percentage and requires at least 50% average efficiency for the relevant fraction. | For example, ePM1 50% is an ISO 16890 classification, not a direct conversion to MERV. |
| Both systems | Cross-standard comparison | Different test methods and reporting approaches | ASHRAE 52.2 assigns MERV using particle-size efficiency tests; ISO 16890 reports ePM classes based on particulate-matter fractions and its prescribed test procedure. | There is no exact one-to-one conversion. Request the relevant test report and compare operating airflow and pressure drop. |