| 1 | Supplier Profile 01 | 72.5–420 kV | IEC 61869-3; IEC 61869-1 | 0.1; 0.2; 0.5 | 3P; 6P | 50–200 VA | 100/√3 V; 110/√3 V; 100 V; 110 V | IEC 60071-1 and IEC 60071-2 insulation-coordination principles; routine and type tests per IEC 61869 | Indoor or outdoor; oil-paper or cast-resin construction depending on voltage class | Transmission substations, revenue metering, busbar protection and transformer differential protection |
| 2 | Supplier Profile 02 | 36–245 kV | IEC 61869-3; IEC 61869-1 | 0.2; 0.5; 0.5S | 3P; 6P | 15–150 VA | 100/√3 V; 110/√3 V; 120/√3 V | Power-frequency withstand, lightning impulse withstand and partial-discharge testing where applicable | Outdoor oil-insulated designs commonly used above medium voltage | Grid substations, feeder measurement and protection circuits requiring stable ratio accuracy |
| 3 | Supplier Profile 03 | 3.6–145 kV | IEC 61869-3; regional utility specifications | 0.2; 0.5; 1.0 | 3P; 6P | 10–100 VA | 100 V; 110 V; 115 V; 120 V | Routine ratio, polarity, excitation and insulation tests; type-test evidence should be requested by project | Cast-resin units common for indoor switchgear; oil-insulated units available for higher voltages | Distribution substations, industrial plants and medium-voltage switchgear |
| 4 | Supplier Profile 04 | 72.5–245 kV | IEEE C57.13; IEC 61869-3 options | 0.15; 0.3; 0.6 | IEEE protection classes such as 0.3 or 0.6; IEC 3P/6P where specified | 25–200 VA | 115/√3 V; 120/√3 V; 115 V; 120 V | IEEE insulation and accuracy requirements or IEC test requirements, according to the project specification | Outdoor designs commonly use sealed oil-filled construction | North American-style substations, protection panels and utility metering |
| 5 | Supplier Profile 05 | 12–72.5 kV | IEC 61869-3; IEC 62271 interface requirements where integrated in switchgear | 0.2; 0.5 | 3P; 6P | 10–75 VA | 100/√3 V; 110/√3 V; 100 V; 110 V | Power-frequency withstand and partial-discharge performance are important for compact indoor assemblies | Cast-resin insulation; indoor installation; compact dimensions | Metal-enclosed switchgear, renewable-energy collector substations and commercial facilities |
| 6 | Supplier Profile 06 | 3.6–36 kV | IEC 61869-3; IEC 61869-1 | 0.5; 1.0 | 3P; 6P | 5–50 VA | 100/√3 V; 110/√3 V; 100 V | Routine dielectric, ratio, polarity and accuracy tests; project-specific type-test documentation required | Cast-resin or air-insulated indoor construction | Industrial distribution, motor-control centers and general-purpose feeder protection |
| 7 | Supplier Profile 07 | 72.5–420 kV | IEC 61869-3; IEC 60071 insulation coordination | 0.2; 0.5; 0.5S | 3P; 6P | 50–300 VA | 100/√3 V; 110/√3 V; 100 V; 110 V | Lightning impulse, switching impulse for applicable high-voltage classes, power-frequency and partial-discharge tests | Outdoor oil-paper insulation; designed for high-voltage transmission environments | Transmission lines, high-voltage busbars and utility-grade measurement systems |
| 8 | Supplier Profile 08 | 12–245 kV | IEC 61869-3; IEEE C57.13 options | 0.2; 0.3; 0.5 | 3P; 6P; IEEE protection classes by specification | 15–150 VA | 100/√3 V; 110/√3 V; 115/√3 V; 120/√3 V | Applicable IEC or IEEE dielectric, accuracy and thermal-performance tests | Indoor cast-resin and outdoor oil-insulated configurations | Mixed-standard projects, utility upgrades and industrial substations |
| 9 | Supplier Profile 09 | 3.6–52 kV | IEC 61869-3; IEC 62271 for switchgear integration | 0.5; 1.0 | 3P; 6P | 5–50 VA | 100 V; 110 V; 120 V | Routine insulation, ratio, polarity, burden and accuracy verification | Indoor cast-resin construction with low-maintenance requirements | Renewable-energy plants, data centers, commercial buildings and medium-voltage networks |
| 10 | Supplier Profile 10 | 12–145 kV | IEC 61869-3; applicable national utility standards | 0.2; 0.5; 1.0 | 3P; 6P | 10–100 VA | 100/√3 V; 110/√3 V; 100 V; 110 V | Type and routine test certificates should confirm dielectric strength, accuracy and environmental suitability | Indoor cast-resin or outdoor oil-insulated configurations | Distribution utilities, industrial substations and cost-sensitive retrofit projects |