| 63 A frame | 16–63 A | 2P, 3P, 4P | 240/415 V AC; some designs up to 690 V AC | Typically 18–36 kA | Small feeders, pumps, HVAC branches, commercial distribution | Use when the calculated design current is normally below 50 A and the available fault current is within the breaker’s interrupting rating. |
| 100 A frame | 40–100 A | 2P, 3P, 4P | 240/415 V AC; some designs up to 690 V AC | Typically 25–50 kA | Sub-distribution boards, motor feeders, small commercial panels | Select an adjustable trip unit when the load current is close to the frame rating or coordination with downstream protection is required. |
| 160 A frame | 80–160 A | 3P, 4P | 415 V AC; commonly 690 V AC maximum | Typically 25–50 kA | Main feeders for workshops, retail buildings, and light industrial loads | Confirm cable ampacity, installation derating, motor starting current, and ambient-temperature correction. |
| 250 A frame | 125–250 A | 3P, 4P | 415 V AC; commonly 690 V AC maximum | Typically 36–65 kA | Building mains, larger HVAC systems, process equipment, generator feeders | The MCCB long-time pickup should protect the conductors without exceeding their permitted ampacity. |
| 400 A frame | 200–400 A | 3P, 4P | 415 V AC; commonly 690 V AC maximum | Typically 36–65 kA | Industrial distribution, large motor control centers, transformer secondary feeders | Check the transformer or generator prospective short-circuit current before selecting the Icu or Ics value. |
| 630 A frame | 315–630 A | 3P, 4P | 415 V AC; commonly 690 V AC maximum | Typically 50–85 kA | Large industrial feeders, data-center distribution, high-capacity switchboards | Use electronic protection when accurate long-time, short-time, instantaneous, or ground-fault settings are needed. |
| 800 A frame | 400–800 A | 3P, 4P | 415 V AC; commonly 690 V AC maximum | Typically 50–100 kA | Main switchboards, large commercial facilities, industrial plant incomers | Verify busbar withstand, enclosure temperature rise, connection method, and discrimination with downstream breakers. |
| 1,250 A frame | 630–1,250 A | 3P, 4P | 415 V AC; commonly 690 V AC maximum | Typically 65–100 kA | Large facility incomers, utility distribution, high-power industrial systems | Confirm continuous load, harmonic heating, neutral loading, short-circuit withstand, and required selectivity. |
| 1,600 A frame | 800–1,600 A | 3P, 4P | 415 V AC; commonly 690 V AC maximum | Typically 65–100 kA | High-capacity mains, large transformers, industrial power distribution | A detailed short-circuit study and coordination study should be completed before final selection. |