| By electrical function | Step-up transformer | Raises AC voltage from the primary winding to the secondary winding while transferring power at the system frequency. | Power-generation connections and renewable-energy installations where output voltage must be raised for transmission or grid interconnection. | Confirm input and output voltages, rated power, frequency, insulation level, vector group, and applicable grid requirements. |
| By electrical function | Step-down transformer | Reduces AC voltage to a level suitable for distribution, industrial equipment, or end users. | Distribution networks, commercial buildings, factories, and equipment supply. | Check the required secondary voltage, load profile, short-circuit impedance, tap range, and expected ambient conditions. |
| By grid role | Power transformer | Designed for high-voltage transmission or large substations, often operating near rated load and at high power levels. | Transmission substations, large power plants, and major grid interconnections. | Assess voltage and power ratings, cooling arrangement, loss values, insulation coordination, and transport limits. |
| By grid role | Distribution transformer | Converts distribution-system voltage to a lower utilization voltage; commonly designed for continuous service with varying loads. | Utility distribution, residential areas, commercial sites, and light industry. | Compare no-load and load losses, expected loading, installation location, enclosure, and local efficiency requirements. |
| By winding design | Autotransformer | Uses a shared winding for primary and secondary circuits, providing a compact and material-efficient voltage ratio when electrical isolation is not required. | Interconnecting systems with similar voltage levels, motor starting, and voltage regulation. | It does not provide galvanic isolation. Verify the voltage ratio, grounding arrangement, fault levels, and system protection requirements. |
| By winding design | Isolation transformer | Has separate primary and secondary windings to provide electrical isolation between circuits; the voltage ratio may be 1:1 or another specified ratio. | Medical and laboratory installations, maintenance supplies, control circuits, and sensitive equipment. | Specify isolation requirements, shielding if needed, rated capacity, leakage limits, and the applicable safety standard. |
| By measurement function | Current transformer (CT) | Produces a reduced secondary current proportional to primary current for measurement or protective relays. | Switchgear, metering panels, substations, and protection systems. | Choose the ratio, accuracy class, burden, insulation level, and protection or metering duty. Never leave an energized CT secondary open-circuited. |
| By measurement function | Voltage transformer (VT/PT) | Produces a reduced secondary voltage proportional to primary voltage for measurement, monitoring, and protection. | High-voltage switchgear, substations, revenue metering, and relay circuits. | Confirm voltage ratio, accuracy class, burden, connection method, insulation level, and whether the design is intended for metering or protection. |
| By core construction | Core-type transformer | Windings are arranged around the core limbs. This is a common construction for many power and distribution transformers. | Utility, industrial, and commercial AC power systems. | Core construction alone does not determine capacity or performance; compare the complete electrical, thermal, and insulation specifications. |
| By core construction | Shell-type transformer | The core surrounds a substantial portion of the windings. This arrangement can provide mechanical support and is used in selected power and special-purpose designs. | Applications requiring particular winding support or construction characteristics, including some industrial and special-purpose units. | Evaluate short-circuit strength, cooling, dimensions, maintenance access, and the manufacturer's tested design data. |
| By insulation and cooling | Oil-immersed transformer | Active parts are immersed in insulating liquid, which provides insulation and transfers heat to the cooling system. | Outdoor substations, utility distribution, and many medium- or high-capacity installations. | Consider fire protection, containment, liquid type, environmental rules, maintenance, and the specified cooling method. |
| By insulation and cooling | Dry-type transformer | Uses air and solid insulation rather than an insulating liquid; designs may be ventilated or cast-resin. | Indoor buildings, commercial facilities, tunnels, and sites where liquid containment is undesirable or restricted. | Check ventilation, enclosure rating, temperature rise, fire and smoke requirements, noise limits, and installation environment. |
| By output requirement | Rectifier transformer | Supplies a rectifier system and may include winding arrangements or phase shifts suited to the converter circuit. | Industrial DC supplies, electrochemical processes, and certain traction or process installations. | Specify converter topology, harmonic duty, number of pulses, load cycle, DC output requirements, and cooling needs. |
| By application | Furnace transformer | Designed for the high currents, low secondary voltages, and demanding operating cycles associated with electric furnaces. | Electric arc furnaces, induction furnaces, and other heavy thermal processes. | Provide the furnace duty cycle, current range, impedance requirements, short-circuit conditions, and cooling arrangement. |
| By application | Traction transformer | Designed to supply railway or other electric traction systems, with requirements shaped by the traction power architecture. | Rail vehicles, railway substations, and traction power networks. | Confirm supply system, onboard or wayside installation, vibration conditions, duty cycle, insulation, and relevant railway standards. |